{"ok":true,"generatedAt":"2026-11-27","cluster":{"slug":"500","rank":"01","name":"500 卡智算集群","englishName":"512-GPU AI CLUSTER","gpuCount":512,"subtitle":"标准 512× H100/H200 · 64 节点 × 8 卡 / 2 个 SU 可扩展单元","summary":"面向 7B–70B 模型微调、行业预训练与混合推理的双 SU 智算单元；以 16 个计算柜、双平面 NDR 400G 和全闪并行存储构成标准交付边界。","defaultPlatform":"h100-80g","suCount":2,"dataHalls":1,"floorDimensionsM":"28 × 18 m（含网络与液冷列）","racks":{"compute":16,"networkStorage":2,"cdu":2,"total":20},"network":{"architecture":"2-Tier Rail-Optimized Fat-Tree InfiniBand NDR 400G","leaf":16,"spine":8,"core":0,"ratio":"1:1 无收敛","optics":1024,"opticType":"400G/800G OSFP","fiberCores":3072,"trunkKm":3.2,"description":"每台 8 卡节点的 GPU 0…7 分别进入 8 条独立 Rail；16 台 QM9700 Leaf 与 8 台 QM9700 Spine 构成两级无阻塞胖树。"},"power":{"itMw":0.72,"facilityMw":0.85,"rackKw":40,"airRackKw":32,"pue":1.18,"grid":"10kV 双路市电馈线","backup":"1×1.2MW 柴油发电机","annualElectricityCny":5956800},"cooling":{"type":"DLC 冷板液冷（可选 32kW 高密度风冷）","primarySupplyC":28,"secondarySupplyC":32,"secondaryReturnC":42,"cdu":2,"description":"闭式冷却塔 + 2× CDU；单柜设计 40kW，N+1 泵组，双路 Manifold。"},"storage":{"capacityPb":1.5,"bandwidthGBs":180,"type":"All-NVMe Lustre / DeepSeek 3FS","checkpoint":"180 GB/s 聚合读写"},"compute":{"fp8Pflops":1013,"vramTbH100":40.96,"vramTbH200":72.19,"training":"7B–70B 全参训练 / 70B–200B 微调"},"economics":{"capexCny":125000000,"capexLabel":"约 ¥1.25 亿（H100 标准版）","alternateCapexLabel":"约 ¥3,800 万（512× RTX 5090 经济推理版）"},"operations":{"mtbf":"约 3.8 天/次 GPU 或光模块硬件事件","incidentsPerDay":0.26,"recovery":"自动隔离故障节点，最近一次 Checkpoint 恢复 < 5 分钟","mfu":"70B 训练 MFU 42%–49%"},"capexBom":[["HGX H100 计算节点","64 节点 × 8 GPU",86000000,"含 NVSwitch、双 CPU、2TB DDR5 与本地 NVMe"],["NDR 400G 网络","16 Leaf + 8 Spine + 1,024 光模块",12000000,"含 AOC/MPO 光纤与 Rail-Optimized 布线"],["全闪并行存储","1.5PB / 180GB/s",5000000,"Lustre 或 3FS，元数据双活"],["直接液冷系统","2 CDU + Manifold + 冷板",4000000,"含闭式冷却塔、泵组与漏液检测"],["供配电与柴发","10kV / UPS / 1.2MW",9000000,"双路馈线、智能母线与后备电源"],["机房工程与机柜","20 Racks / 冷通道",5000000,"承重、消防、桥架与动环"],["软件集成与验收","调度 / 并行训练 / 驻场",4000000,"Slurm/K8s、监控、NCCL 调优与验收"]],"playbook":["按 SU 隔离 256 卡故障域，训练任务配置 node health check 与 NCCL 异步错误上报。","每 15–30 分钟异步 Checkpoint；元数据写入独立 SSD，训练数据分片预取。","每日校验光模块 FEC、BER、温度与收发光功率，劣化端口预先替换。"]}}